| Model | H3CR-AP AC24-48/DC12-48 |
|---|
| Rated power supply voltage | 24 to 48 VAC 50/60 Hz12 to 48 VDC Ripple 20% max. (If power supply incorporates a single-phase full-wave rectifier) |
|---|
| Allowable voltage variable range | 85 to 110% of rated voltage (90 to 110% at 12 to 48 VDC) |
|---|
| Input signals | Start |
|---|
| Input method | Voltage input |
|---|
| Voltage input | High level: 20.4 to 52.8 VAC/10.8 to 52.8 VDCLow level: 0 to 2.4 VAC/0 to 1.2 VDC |
|---|
| Power consumption | Relay ON: Approx. 0.9 W (at 24 VDC)/Relay OFF: Approx. 0.3 W (at 24 VDC) |
|---|
| Reset voltage | 10% max. of rated supply voltage |
|---|
| Number of time ranges | 18 |
|---|
| Operation mode | ON delay, Flicker OFF start, Flicker ON start, Signal ON/OFF delay, Signal OFF delay, Interval, Signal ON/OFF delay, One shot output |
|---|
| Control output (Type) | Time-limit: DPDT |
|---|
| Control output (Contact output) | Resistive load: 250 VAC 5 A (cosφ=1)/5 A at 30 VDC/0.15 A at 125 VDCInductive load (Reference value): 2 A at 250 VAC (cosφ=0.4)/3 A at 30 VDC (L/R=7 ms)Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value) |
|---|
| Operating resetting | Time-limit operation/Self-reset |
|---|
| Ambient temperature range | Operating: -10 to 55 ℃ (with no icing)Storage: -25 to 65 ℃ (with no icing) |
|---|
| Ambient humidity range | Operating: 35 to 85 % |
|---|
| Accuracy of operating time | ±0.2% FS max.±0.2% ±10 ms in a range of 1.2 s and 3 s |
|---|
| Setting error | ±5% FS ±50 ms max.The value is ±5% FS +100 ms to -0 ms max. when the C, D, or G mode signal |
|---|
| Reset time | 0.1 s max. |
|---|
| Influence of voltage | ±0.2% FS max.±0.2% ±10 ms in a range of 1.2 s and 3 s |
|---|
| Influence of temperature | ±1% FS max. (±1% ±10 ms in a range of 1.2 s and 3 s) |
|---|
| Insulation resistance | 100 MΩ min. (at 500 VDC) |
|---|
| Dielectric strength | Between current carrying metal parts and non-current carrying metal parts: 2,000 VAC 50/60 Hz 1 minBetween control output terminals and operating circuit: 2,000 VAC 50/60 Hz 1 minBetween contacts of different polarity: 2,000 VAC 50/60 Hz 1 minBetween non-continuous contacts: 1,000 VAC 50/60 Hz 1 minBetween input and control output/operation circuit: 2,000 VAC 50/60 Hz 1 min |
|---|
| Impulse withstand voltage | Between power terminals: 1 kVBetween current carrying terminals and exposed non-current carrying metal parts: 1.5 kV |
|---|
| Noise immunity | ±1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) |
|---|
| Static immunity | Mulfunction: 8 kV, Destruction: 15 kV |
|---|
| Vibration resistance | Destruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 hMalfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min |
|---|
| Shock resistance | Destruction: 1,000 m/s2, 3 times each in 6 directionsMalfunction: 100 m/s2, 3 times each in 6 directions |
|---|
| Life expectancy (relay output) | Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1800 operations/h)Mechanical: 20 million operations min. (under no load at 1,800 operations/h) |
|---|
| Degree of protection | Panel surface: IP40Terminals: IP00 |
|---|
| Connecting method | 11-pin round socket |
|---|
| Case color | Munsell 5Y7/1 |
|---|
| Weight | Approx. 90 g |
|---|
| Accessories | Instruction manual, Compliance information sheet |
|---|
| Applicable socket | P2CF-11/ P2CF-11-E/ P3GA-11/ PL11/ PL11-Q/ PLE11-0 |
|---|